CALCULATORS

Calculate the Larson-Skold index

The Larson-Skold index relates chloride and sulphate to the alkalinity of the water and estimates its corrosivity towards steel and cast iron. It is useful for process water, cooling water and distribution networks with metal pipes.

Larson-Skold index

Indicative result. For a diagnosis of your installation, measure continuously or contact us.

SEE OTHER CALCULATED PARAMETERS

How it is calculated

  • Larson-Skold index: (Cl⁻ + SO₄²⁻)/alkalinity in meq/L. Above 0.8: steel corrosion possible; above 1.2: high. Chloride and sulphate estimated from conductivity.

Measure these data continuously

With our IoT probes, sensors and equipment you have the data in real time on any device, and the panel calculates this value on its own and warns you before problems appear.

Applications whose panel (dashboard) calculates it continuously: Chemical industry (panel · ROI) · Pulp, paper and board (panel · ROI) · Steel and metallurgical industry (panel · ROI) · Glass and cement manufacturing (panel · ROI) · Ceramics industry (panel · ROI) · Automotive and transport industry (panel · ROI) · Aerospace and aviation (panel · ROI) · Industrial laundries (panel · ROI)

See the panel model · Applications · Langelier index

SEE OTHER CALCULATED PARAMETERS